Welcome to ECBAY
LVQB-132 Outdoor Gas-insulation type 132kv current transformer
LVQB-132 Outdoor Gas-insulation type 132kv current transformer

1, 132kv current transformer 2, safety and prevent the danger of explosion. 3, 20years' sales experience

LVQB-132(110, 66)Outdoor Gas-insulation type 132kv current transformer

1,This product is of F6 gas insulation inversed structure. Primary winding is of penetrating type conducting rod structure; max short time withstand current reaches 63kA/3s

2,Primary winding runs through the center, free of the influence of leakage flux, with measuring accuracy reaching class 0.1 and class 0.2s

3,The upper enclosure is processed from welded aluminum alloy, with metal bursting disc will rapidly release pressure after internal pressure rises to 0.85Mpa, hence improve the product safety and prevent the danger of explosion.

4,Secondary winding is cast in aluminum shielding case by organic materials, hence the secondary circuit will not suffer electric shock caused by insulation breakdown.

5,There are two types of external insulating bushings available for user choice: fiber glass bushing with silicon rubber umbrella skirt: high-strength porcelain properly.

6,Seal rung is made from imported fluorine rubber. Its annual leakage rate is less than 0.5%.

7,Pedestal is of double-layer anticorrosion protection; stainless steel fasteners, nameplate and all other parts are guaranteed be rust-free all the time

8,The pedestal is equipped with density meter which end display internal gas pressure and density and send out signal when internal gas pressure reduce to alarm pressure requesting gas supply.

Technical data

Rated primary voltage

132(110,66)kv

Highest voltage for equipment

145(126,72.5)kv

Rated frequency

50 or 60 Hz

Rated current ratio

2×200-2×3000/5or 1A

Number of secondary windings

1-6

Accuracy of measuring winding

0.2, 0.2s, 0.5, 0.5s

Accuracy of protection winding

5p or 10p

Rated secondary output

20-50va

Accuracy limit factor

15, 20, 25, 30

Instrument security factor

<5 or <10

Partial discharge under 1.2Um/√3Kv

≤5Pc

SF6(20)rated gas pressure

Gas supply pressure

0.4MPa

0.35MPa

Power frequency withstand voltage on primary windings

230(275)kv 200(230)kv 140kv rms

Rated lightning impulse withstand voltage

550(650)kv 450(550)kv   325kv peak

Power frequency withstand voltage between primary sections

3kv rms

Power frequency withstand voltage on earth screen to earth

5kv rms

Power frequency withstand voltage on secondary windings and secondary windings to earth

3kv rms

secondary winding inter-turn withstand voltage

4.5kv peak

Mechanical strength(three direction)

2500N