material: high quality sillicon rubber voltage class:15kV 25Kv 35kV easy installation price: see by contact (very cheap)
Straight Joints
Type ZJTLS
Up to 36 kV
Application
For jointing copper wire screened or copper tape screened three-cores or single-core cable to be laid in air or directly buried.
Table 16
Table X Cable insulation range Use for 8.7/15 kV joint | Cable Insulation Code | Cable Insulation Range | Cable Cross Section | |
Inches | mm | mm2 | ||
A | .67~.79 | 17.0~20.0 | 25,35,50 | |
B | .79~.98 | 20.0~25.0 | 70,95,120 | |
C | .98~1.18 | 25.0~30.0 | 150,185,240 | |
D | 1.18~1.42 | 30.0~36.0 | 300,400 | |
E | 1.42~1.50 | 36.0~38.0 | 500 |
Table 17
Table X Cable insulation range Use for 12/20 kV joint | Cable Insulation Code | Cable Insulation Range | Cable Cross Section | |
Inches | mm | mm2 | ||
A | .79~.98 | 20.0~25.0 | 35,50,70 | |
B | .98~1.18 | 25.0~30.0 | 95,120,150 | |
C | 1.18~1.42 | 30.0~36.0 | 185,240,300 | |
D | 1.42~1.50 | 36.0~38.0 | 400,500 |
Table 18
Table X Cable insulation range Use for 18/30 kV joint 19/33 kV joint | Cable Insulation Code | Cable Insulation Range | Cable Cross Section | |
Inches | mm | mm2 | ||
A | .95~1.06 | 24.0~27.0 | 35 | |
B | 1.02~1.34 | 26.0~34.0 | 50~70 | |
C | 1.18~1.58 | 30.0~40.0 | 95~185 | |
D | 1.54~1.77 | 39.0~45.0 | 240~300 | |
E | 1.73~2.01 | 44.0~51.0 | 400~500 |
Example: A joint is required for a 8.7/15kV, 300mm2 compacted, three core copper tape screen cable with a diameter over core insulation of 30.6mm. Order a ZJTLS15-300/3 –DT joint.