1.Propotional-action control for VAV system 2.1X 0~10V output for an actuator, 2X on/off contact outputs for 2-stage heater.

Power supply

24 VAC±10%  50/60HZ

18VDC~28VDC

Electrical rating

2 amp load per terminal

Sensor

NTC 5K

Temperature control range

5-35 °C  (41°F-95°F)

Accuracy

±0.5 °C (±1°F) @25°C

Analog output

One or two analog outputs

Voltage       DC 0V~DC 10 V

Current       1 mA

Protection class

IP30

Environment condition

Operating temperature: 0 – 50 °C

Operating humidity: 5 – 99% RH

Storage temperature:  -10 – 60 0C

Storage humidity:      <95%RH

Display

LCD

Net Weight

240g

Dimensions

120mm(L)×90mm(W)×24mm(H)

Material and colors:

PC/ABS Fireproofing house with white color

Mounting standard

Mounting on the wall, or 2“×4“/ 65mm×65mm pipe box

1)Room temperature controller for VAV System

Designed to control the VAV terminal with 1X0~10VDC or 2X0~10 VDC output for damper actuators. There are also one or two on/off contact outputs to control one or two-stage electric aux. heater.

2)Enough Setup Options

Many setup options to make it use in all kinds of application, such as the maximum and minimum opening angle of the air damper, the max. limit and the min. limit of temperature and so on.

3)Up to 2 Stage Energizing

Supply one or two-stage electric aux. heaters. Makes temperature controlling more accurate and energy-saving.

4)Large LCD display

Display working status such as room temperature, set temperature level, damper and electric heating status, etc. Make reading and operating easy and accurate.

5)Two Temperature Degree Selectable

Celsius or Fahrenheit degree can be selected.

6)Easy installing

Two parts structure and quick wire terminal block makes installing easily.

7)External Temperature Sensor(optional)

8)Infrared Remote Control (optional)

Remote operating with handle remote controller.

9)0~12 Hours Timer of turning off(optional)

10)RS485 Communication Interface (optional)

RS485 communication interface is selectable and its protocol can be supplied to connect with PC or other systems.