Detailed Product Description
mainly technical parameters
analog output: 4 to 20 mA DC, 0 to 10 mA DC, 1 to 5 V DC, and 0 to 5 V DC
switch output: relay control output -- ON/OFF ( with return difference)
contact capacity: AC220 V/3 A, DC 24 V/5 A (resistive load)
SCR control output -- SCR zero-passing trigger pulse output AC 400 V/0.5 A
SSR output (solid state relay control signal output), 5 to 24 V DC/30 mA
communication: RS-232C, RS-485
band rate: 300 to 9600 bps
measuring range: relative pressure: max.: 0 to 60 MPa, min.: 0 to 20 KPa
absolute pressure: max.: 0 to 60 MPa, min.: 0 to 20 KPa
measuring accuracy: ±0.2% FS or ±0.5 %FS
resolution: ±1 digit
display: -1999 to 9999
ambient temperature: 0 to 50
control/alarm: selectable upper limit, lower limit or up-upper limit, low-lower limit
supply voltage: 90 to 265 V AC (switch power), DC 24 V±2 V (switch power)
structure material: pressure interface: stainless steel
inducing membrane: 316L stainless steel
electronic housing: aluminium alloy or iron
process connection: outer thread G1/2 (inner hole φ10 mm), outer thread M20×1.5 (inner hole φ3 mm), outer thread G1/2 (inner hole φ3 mm), outer thread 1/2 -14 NPT, outer thread M20×1.5 (inner hole φ10 mm)