Welcome to ECBAY
Bi-flow solenoid valve
Bi-flow solenoid valve

Detailed Product Description


SSV series two-way bi-flow solenoid valves are mainly used for the defrosting of wind cooling heat pump refrigeration unit and the defrosting of supermarket refrigerators as well.
The adoption of SSV series can reduce the amount of check valves and solenoid valves in the refrigeration system, which makes system pipeline designs more reasonable.

Operating principle

While energized in coil, the electromagnetic power opens the small orifice. Then the pressure in upside of valve reduced, so the pressure difference between both side of diaphragm happen and lead to diaphragm lift to open the main orifice, the valve flows bi-directionally. While de-energized in the coil, plug stem will drop and close the small orifice because of spring force and its weight. When inlet pressure is higher than outlet pressure across valve, the valve closed. When outlet pressure is higher than inlet pressure across valve, a few medium can flow across the valve in opposite direction.

Technical data
Ambient temperature: -20 ~ 50 .C
Medium temperature: -25 ~ 120 .C
Max. working pressure: 3 MPa
Available medium: R134a,R22,R407C,R404A/507,air,water and oil.
Optional voltage of solenoid coils:
A.C.: 24V,36V,110V,220V,380V.
D.C.:12V,24V,110V,220V
Type and data

Connection
form

Model

Connection
dimension
(in.)

Kv value
(m3/h)

Opening diff.
pressure
(MPa)

Dimension
(mm)

Min.

Max.

A.C.

D.C.

Length

Wide

Height

Flare
SAE

SSV6

5/16

0.4

0.005

2.1

1.7

85

45

97

SSV8

3/8

1

85

45

97

SSV10A

1/2

1.8

85

45

97

SSV13A

5/8

3

89

45

97

SSV16

3/4

4.5

119

60

120

SSV19

7/8

5

119

60

120

Solder
ODF

SSV6W

5/16

0.4

125

45

97

SSV8W

3/8

1

125

45

97

SSV10AW

1/2

1.8

125

45

97

SSV13AW

5/8

3

150

45

97

SSV16W

3/4

4.5

185

60

120

SSV19W

7/8

5

190

60

120

SSV25W

1-1/8

9.5

0.03

232

72

120

1-3/8

250

72

120

SSV32W

1-3/8

15

281

86

130

1-5/8

281

86

130

The Kv value is the water flow in m3/h at a pressure drop across valve of 0.1MPa,ρ=1000 kg/m3
Letters after the model: A means improved type,W means solder ODF,F means waist flange,K means normal opened valves.