Welcome to ECBAY
S(B)H16-M.D 11kv buried environmental protection and energy conservation amorphous core street lamp transformer
S(B)H16-M.D 11kv buried environmental protection and energy conservation amorphous core street lamp transformer

1. power distribution transformer 2. Accords to GB/T7595 JB/T3837-1988 IEC60076 3. three years warranty 4.high quality

General

The transformer is low loss, whole sealing, corrosion, water proof, reliable operation and can be used in the distribution transformer and other high-protection requirements.

Structure features:

1, Good corrosion resistance, sealed, water proof and shell is produced by special steel, can be installed directly in the ground. Protection level is IP68. For a period of time, the transformer can still keep working with parts immersed in the water

2. The current limiting fuse is installed in the high voltage side for protection, in-out by cable. The interface is sealed to ensure product reliability and security.

3. Amorphous alloy core with rolled trip, no-load loss is 75-80% lower than S9 series transformer

4. Taking into account the special circumstances of ventilation cooling, surface temperature rise of oil and winding temperature rise than the national standard dropped 10K

/

This series transformer is mainly used for roads, bridges, tunnels and also the lighting system. Underground installation would not affect the overall landscape and urban greening

Structural features

1. Good corrosion resistance, sealed, water proof and shell is made of special steel, can be installed directly in the ground. Protection level is P68, for a period of time, the transformer can still keep working with parts immersed in water

2. The current limiting fuse is installed in the high voltage side for protection, in-out by cable, the interface is sealed to ensure product reliability and security

3. Amorphous alloy core with rolled strip. No-load loss is 75-80% lower than S9 series transformer

High voltage(KV):6/10

Low voltage(KV):0.4

High voltage tapping range:±5

Impedance voltage(%):4

Rated capacity(KVA)

No-load loss(W)

Load loss(W)

No-load current(%)

Dimension(mm)

Install center(mm)

Oil weight(KG)

Overall weight(KG)

5

12

185

1.7

940x700x940

400x600/4-φ14

155

300

10

16

290

1.5

940x700x940

400x600/4-φ14

145

340

16

19

390

1.2

940x700x940

400x600/4-φ14

140

380

25

25

530

1.1

940x700x940

400x600/4-φ14

135

425

30

28

600

1.0

940x700x940

400x600/4-φ14

130

450

50

38

870

0.9

1020x730x990

400x600/4-φ14

140

575

80

50

1250

0.8

1100x795x1025

400x600/4-φ14

235

850

100

58

1500

0.7

1100x795x1025

400x600/4-φ14

230

885