GW5 Ⅲ Series disconnector is researched and developed by ourselves based on over 20 years production GW5 II , a new-style disconnector which has reached the perfect requirements of SGCC, mainly focusing on design perfection in loop circuit heating, improvement in conductive reliability, prevention for driving parts failure, protection against rust and corrosion on bearing pedestal, simplified installation on construction site, debugging, etc. GW5 Ⅲ Series is 2 columns, horizontally rotary, single break type disconnector, including 3 single poles, of which is V-shaped and double column structure. It is constituted with pedestal, pillar insulator and conductive part. There are 2 pillar insulators with an angle of 50 degree respectively fixed on the bearing pedestal connected with the base, driven by a set of 4 linkages mechanism. Conductive blade consists of left and right contact-head, which separately fixed on pillar insulator.

Product Features

1), it adopts external-pressured contact-finger structure, appearance with silver plated treatment. Conductive linkage adopts square-shaped aluminum tube, enlarging heating dissipation area and improving conductive reliability with tin-plated treatment.

2), it adopts a new type contact head and finger, larger contacting area compared with the original contact head and finger, enables it to better heat dissipation, eliminate impact from skin effect, good self-cleaning and counter-corrosion. This structure makes the contact head deeply inserted into the finger, which greatly improve reliability of electric conductivity.

3), wiring block and wiring terminal are connected with fixed flexible connection. The wiring terminal upper ends and lower ends adopt isolating shaft to ensure reliable conductivity and flexible rotation. Wiring terminal and the outlet column adopts an integrated structure, reducing a possible heat dissipation spot.

4), Bearing pedestal is designed with wholly-sealed structure, adopting up-down double channel sealed, which can effectively prevent rain and dust from corrosion to rotating bearing. The surface of bearing pedestal will be painted with sufficient wide temperature lubricant grease of which working environment range from -60°C to +120°C, in order to avoid lubrication malfunction in extremely hot and cold regions.

  

5), all rotary shaft pins are made of stainless steel. Rotary parts are imported IGUS Engineering Plastic Bearings from Germany instead of copper shaft. The transmission system adopts stainless steel joint bearing, which can effectively avoid rust on rotary shaft and ensure long-term easy and flexible operation of the product.

Product Classification and Main Technical Specification

1), product classification

Voltage level: 40.5kV, 72.5kV, 126kV.

Current level: 1250A, 2000A, 3150A.

Auxiliary earthing switch type: none earthing switch, left earthing switch, right earthing switch, double earthing switches.

Rotation type: rotation with an angle of 90 degree, rotation with an angle of 180 degree.

Technical SpecificationsProduct TypeGW4G-126
Rated voltage kV 126
The rated current A 1250, 2000
DisconnectorRated peak withstand current kA100
Rated short-time withstand current (RMS)kA40
Rated short circuit duration s4
Grounding switchRated peak withstand current kA100
Rated short-time withstand current (RMS)kA40
Rated short circuit duration s4
Rated short-time power frequency withstand voltage (RMS) kVto earth230
across open contacts230+70
Rated lightning impulse withstand voltage (peak) kVto earth550
across open contacts550+100
minimum clearance in 1 min power frequency withstand voltage when ground blade closing to live part of disconnector 164
rated terminal static mechanic load Nlongitudinal level1000, 1250
Horizontal level750
Vertical force1000
Earthing switch Micro-Inductive current switching abilityElectromagnetic induced current (current/voltage)50/0.5(A type) 100/0.6(B type)
Static induced current (current/voltage)0.4/3(A type) 5/6(B type)
Switching times10 times
switching capacitance current A 2
switching inductance current A 1
switching busbar for current transfer A (busbar transfer voltage 100V) 400V, 2500A, 100 times
Radio interference level less than 500 μV
Mechanical life 3000
single pole weight (kg) 350
Note: All applied to an altitude of 2000m 