Welcome to ECBAY
Compact busbar trunking system
Compact busbar trunking system

Compact busbar trunking system 1 Professional manufacturer 2 ISO9001 and ISO 14001 certificate 3 CCC and CE certificate

compact busbar trunking system

1. Current Rating: 250 A to 6000 A

2. Ingress protection of IP42/IP55

3. Excellent short circuit ratings [upto 1000 A]

4. Standard lengths of 3m / 2m / 1m

5. System Voltage: AC380V/690 V

6. Conductor material: High conductivity Copper bar

7. Halogen free, fire retardant Class-H-Epoxy insulation

8. Tap - off units are suitable for MCCBs or SDFs or MCBs

9. Configuration of 3P3W / 3P4W / 3P5W with or without integral earth

10. Flexible system direction to meet cross arrangement

11. Can be re-used after disassemble.

Competitive Advantages:

1 Well and High Quality Control

2 Prompt Delivery

3 Customer's Design and Logo are Welcome

4 Competitive Prices

5 Small Order Acceptable

6 ODM Accepted

7 OEM Accepted

8 Packaging Detail Standard export packaging or customerized packaging

Description:

XLV series busbar trunking system is advanced and energy saving type developed by Zhenda. It adopts British Henrob and Germany EPRESS self-piercing riveting technology, the overall structure of enclosure are riveted together automatically, ensure high degree of automation. The use of hydraulic pressure makes the overall strength of busway being substantially enhanced, and has a good sealing effect and anti-seepage feature.

Besides above, it has features below:

1. Flexible system direction to meet cross arrangement

2. Space saving

3. Can be re-using after disassembled.

4. High short-circuit strength and protection degree.

5. Both nut tightening and self-piercing riveting technology are available.

6. It adopts floor plates to double the heat dispersion.

7. Compact construction, good heat dispersion, low impedance, reliable and easy to installation and maintenance.

Technical parameter:

Rated current(A)

250

400

630

800

1000

1250

1350

1600

2000

2300

2500

3150

3800

4000

4500

5000

Rated voltage

AC380/690V

Rated insulated voltage

660-1000V

Rated frequency

50/60Hz

Rated short-time withstand current

30(KA)

80(KA)

100(KA)

Overvoltage category/Pollution degree

III/3

Protection degree

IP40,IP54,IP65

Weight(kg/m)

9

11.5

12.5

15

18

23

25

32

40

48

55

69

83

90

102

116

Impedance of relative neutral line at temperature 35°C and frequency 50Hz

Resistance

0.12

0.105

0.092

0.081

0.062

0.05

0.038

0.029

0.023

0.018

0.015

0.014

0.012

0.011

0.009

0.008

Reactor

0.051

0.045

0.039

0.033

0.027

0.022

0.019

0.014

0.011

0.009

0.008

0.007

0.006

0.005

0.004

0.004

Impedance

0.13

0.114

0.101

0.087

0.068

0.055

0.042

0.032

0.025

0.02

0.017

0.016

0.013

0.012

0.01

0.009

  Comparison between enclosure and conductor section area (equivalent with aluminum enclsoure)

Current(A)PE section area
400320%
630274%
800240%
1000305%
1250235%
1400211%
1600187%
2000157%
2300136%
2500121%
3100221%
3800197%
4300184%
5000171%

  Tap - off units are suitable for MCCBs or SDFs or MCBs

Protection unitCurrent(A)H(mm)W(mm)L(mm)
Fuse16-25310250500
Switch32-160270360450
200-400340390550
630-800370550700
Breaker16-200310250550
250-400310340650
630-800350340950

Certificate

Functional units

Equipments

Office in Shanghai

Factory

Compact busbar trunking system

Ads by Google


About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.