XLPE insulated power cable
XLPE insulated power cable

The cable is used in electric transmission and distribution system operating at rated voltage of 0.6~1kV.

35kV or Lower XLPE Insulation Power Cable

1.application

It is suitable for fixed laying in power transmission and distribution lines with AC 50Hz and Voltage rating of 0.6/1KV., 1.8/3, 3.6/6, 6/6, 6/10, 8.7/10, 8.7/15, 12/20, 21/35, 26/35kV.

Executive Standard

1.1      It is manufactured according to IEC502 standard.

1.2      The flame-retardant XLPE insulated power cable is manufactured according to the enterprise standards.Its flame-retardant character complies with IEC60332-3.

1.3      The low smoke & low-halogen flame-retardant XLPE insulated power cable is manufactured according to the enterprise standards.Its flame-retardant character complies with GB/T18380.3, IEC61034.

2. Model Explanation

  ÿ   ð   ð   ÿ   ð   ÿ   ð   ð   ÿ

9   8   7   6   5   4   3     2   1

                                                                            

1. Section area of conductor mm2

2. Core No.

3. Rated voltage Uo/U

4. External covering

5. Armor layer

6. Sheath

7. Conductor

8. Insulation

9. Flame-retardant character

3. Explanation of Code In The Type

         Iem                         Code                 Explanation

   Flame-retardant                                            Non flame-retardant

       Character                     ZR      Flame-retardant 3 classes including a,b,c

                                     WD               Low smoke & halogen-free

                                    DD               Low smoke & Low halogen

       Insulation                      YJ                             XLPE

       Conductor                     T                           Cu conductor

                                     L                          Al conductor

     Sheath or inner                    V                PVC

         Sheath                       Y               Polyolefin

                                                           PE

     Armor layer                      2                   Double steel armor

                                       3                    Thin steel wire armor

                                       4                    Thick steel wire armor

   External covering                    2                   PVC

                                      3                   Pe polyolefin

4. Type and Designation

             Type                           Designation

     YJY YJLV                       Power cable with CU/AL conductor.XLPE insulation and PVC sheath.

     YJY YJLY                               Power cable with CU/AL conductor.XLPE insulation and PE sheath.

     YJV22 YJLV22                           Power cable with CU/AL conductor.XLPE insulation steel tape armor and PVC sheath.

     YJV23 YJLV23                           Power cable with CU/AL conductor.XLPE insulation steel tape armor and PE sheath.

     YJV32 YJLV32                           Power cable with CU/AL conductor.XLPE insulation thin steel wire armor and PVC sheath.

     YJV33 YJLV33                           Power cable with CU/AL conductor.XLPE insulation thin steel wire armor and PE sheath.

     YJV42 YJLV42                           Power cable with CU/AL conductor.XLPE insulation thick steel wire armor and PVC sheath.

     YJV43 YJLV43                           Power cable with CU/AL conductor.XLPE insulation thick steel wire armor and PE sheath.

     ZR-YJV ZR-YJLV                         Flame-retardant Power cable with CU/AL conductor.XLPE insulation and PVC sheath.

     ZR-YJ V22 ZR-YJL V22                   Flame-retardant Power cable with CU/AL conductor.XLPE insulation steel tape armor and PVC sheath.

     ZR-YJ V32 ZR-YJL V32                   Flame-retardant Power cable with CU/AL conductor.XLPE insulation thin steel wire armor and PVC sheath.

     ZR-YJ V42 ZR-YJL V42                   Flame-retardant Power cable with CU/AL conductor.XLPE insulation thick steel wire armor and PVC sheath.

     DDZ-YJV DDZ-YJLV       Low-smoke&low halogen flame-retardant Power cable with CU/AL conductor.XLPE insulation steel tape armor and PVC sheath.

     DDZA-YJ V22 DDZA-YJL V22   Low-smoke&low halogen flame-retardant Power cable with CU/AL conductor.XLPE insulation thin steel wire armor and PVC sheath.

     DDZA-YJ V32 DDZA-YJL V32       Low-smoke&low halogen flame-retardant Power cable with CU/AL conductor.XLPE insulation thick steel wire armor and PVC sheath.

DDZA-YJ V42 DDZA-YJLV42         Low-smoke&low halogen flame-retardant Power cable with CU/AL conductor. XLPE insulation thick steel wire armor and PVC sheath.

WDZA-YJY     WDZA-YJLV       Low-smoke&low halogen flame-retardant Power cable with CU/AL conductor. XLPE insulation and polyolefin sheath.

  

WDZA- YJV23 WDZA- YJV23      Low-smoke&low halogen flame-retardant Power cable with CU/AL conductor. XLPE insulation steel tape armor and polyolefin sheath..

WDZA- YJV33       WDZA- YJL V33         Low-smoke&low halogen flame-retardant Power cable with CU/AL conductor. XLPE insulation thin steel wire armor and polyolefin sheath..

WDZA- YJV43       WDZA- YJL V43        Low-smoke&low halogen flame-retardant Power cable with CU/AL conductor. XLPE insulation thin steel wire armor and polyolefin sheath.

5. Using Features

1. Rated voltage Uo\U includes 0.6/1kV, 1.83/3kV, 3.6kV, 6/6kV, 6/10kV, 8.7/10kV, 8.7/15kV, 12/20kV, 21/35kV, 26/35kV.

2. The higest allowed operating temperature of conductor for long-term working is 90 °C. In short-circuit(Max.long-term is no more than 5 seconcls), the peak temperature of conductor is no more than 250         .

3. D.C.resistance of the conductor complies with the stipulations of GB/T3956.

4. The installational ambient temperature should be no lower than 0°C. Otherwise it should be preheated.The min,bending radius should be no smaller than 15 times of cable's outer diameter.

5. The cable is laid without fall restriction.

6. Working frequency voltage test:

for cable with Uo of 3.6kV or lower                   2.5Uo+2kV/5 min without puncture

For cable with Uo of 3.6kV-18kV                     3.5Uo/5min without puncture

For cable with Uo of 21kV and 26kV                  2.5Uo/30 min without puncture

7. Partial discharge test: The discharge volume should be no more than 10pC under1.73Uo for cable.