Welcome to ECBAY
Peroxide Crosslinked PE Cable-purpose Insulating Compounds
Peroxide Crosslinked PE Cable-purpose Insulating Compounds

Peroxide Crosslinked PE Cable-purpose Insulating Compounds

The peroxide crosslinked PE cable-purpose insulating compounds are made mainly from LDPE together with additives such as anti-oxidant and peroxide crosslinking agent through mixing, plasticization and granulation. PreSently YJ-10, YJ-35 and YJW-10, YJW-35 are available, with their applications and performances as follows:

 YJ-10 Peroxide XLPE insulating compound for MV wires and cables up to 10kV (Natural)

S/N

Testing item

Unit

Standard

Typical value

1

Tensile strengh

MPa

≥13.5

23.0

2

Elongation

%

≥350

530

3

Brittleness tempearture             Testing temperature             Brittle capability

°CFail number

-76≤15/30

0

4

Aging in airCircumstance: temperature                       timeChange of tensile properties ≤Change of elongation ≤

°Ch%%

135±2168±20±20

+9+5

5

Hot set elongation    200°C, 0.2MPa, 15min    Elongation under load    Permanent deformation after cooling

%%

≤80≤5

55-2

6

Gel content 

%

≥80

85

7

Dissipation factor 50Hz,20°C

 

≤ 1.0×10-3

2×10-4

8

Dielectric constant 50Hz,20°C

 

≤2.35

2.2

9

DC volume resistivity at 20°C

Ω·m

≥1.0×1014

9×1014

10

Dielectric strength

MV/m

≥25

39

Note: product standard JB/T 10437-2004 XLPE compounds for wired and cables

YJ-35 Peroxide XLPE insulating compound for MV wires and cables up to 35kV (Natural)

S/N

Testing item

Unit

Standard

Typical value

1

Tensile strengh

MPa

≥13.5

23.0

2

Elongation

%

≥300

530

3

Brittleness tempearture          Testing temperature          Brittle capability

°CFail number

-76≤15/30

0

4

Aging in airCircumstance: temperature                       timeChange of tensile properties ≤Change of elongation ≤

°Ch%%

135±2168±20±20

+9+5

5

Hot set elongation        200°C, 0.2MPa, 15min        Elongation under load        Permanent deformation after cooling

%%

≤80≤5

55-2

6

Gel content 

%

≥80

85

7

Dissipation factor 50Hz,20°C

 

≤ 5.0×10-4

2×10-4

8

Dielectric constant 50Hz,20°C

 

≤2.35

2.2

9

DC volume resistivity at 20°C

Ω·m

≥1.0×1014

9×1014

10

Dielectric strength

MV/m

≥25

39

11

Impurity content(0.175~0.250) mm ≥0.250 mm

PCSPCS

≤50

30

 

 

 

 

 

Peroxide Crosslinked PE Cable-purpose Insulating Compounds

Ads by Google


About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.