Welcome to ECBAY
NBR/PVC rubber foam heat insulation tube (pipe) for HVAC
NBR/PVC rubber foam heat insulation tube (pipe) for HVAC

1.low thermal conductivity 2.UL94 BS 476 ASTM E84 approved 3.used for HVAC systems 4.low smoke density 5.easy installation

NBR/PVC rubber foam heat insulation tube for HVAC

 

1.Overview: 

 

All Kingflex elastomeric rubber foam insulations are engineered and manufactured forHVAC and other industrial applications. With closed cell structure Kingflex insulationseffectively retard heat flow and prevent condensation when properly installed. The environmental friendly materials are manufactured without the use of CFC's,HFC's or HCFC's. They are also formaldehyde free, low VOCs,fiber free, dust free and resistant to mold and mildew.

2.Technical data:

Property

Unit

Value

Test Method

Temperature range

°F (°C)

-297~220(-183~105)

-

Density range

Ibs./ft3(kg/m3)

3.0~6.0(48~96)

ASTM D 1622 or D1667

Thermal conductivity

75 °F mean T (24 °C)

Btu·in./h·ft2·°F(W/mK)

0.27(0.039)

ASTM C177 or C518

90 °F mean T (32 °C)

Btu·in./h·ft2·°F(W/mK)

0.276(0.040)

Water vapor permeability

Perm-in (kg/m ·s ·pa)

0.08(1.16 X 10-13)

ASTM E96 procedure A DIN 52615

Flame spread and smoke developed index

25/50

ASTM E84,CAN/ULC S 102

Class 1

BS 476 part 7

V0

UL94

Water absorption, by volume

%

0.2

ASTM C209

Mold growth

-

Meet requirement

UL181

Bacterial resistance

Meet requirement

ASTM G22

Fungi resistance

Meet requirement

ASTM G21/C1338

Resistance to agent chemical

-

Stable performance to agent chemical

-

Ozone resistance

-

good

ASTM D1149

Aging resistance

-

150 hours, slight wrinkles, no cracks, holes or distortion

3.Specification:

Standard wall thickness: 6/9/16/19/25/30mm or 1/4", 3/8", 1/2", 3/4", 1", 1-1/4"

Standard length: 1.83m or 6 feet, 2m

ID range: 6-108mm or 1/4" - 4-1/4"

4.Features or performance:

Protect EnvironmentSave Operating CostControl CondensationIncrease Process EfficiencyReduce Fire RiskImprove AppearanceProtect Workforce

5.Applications:

Kingflex K1 insulation TUBE is used to retard heat transmission and control condensation from chilled-water and refrigeration systems.It also efficiently reduces heat transfer for hot-water plumbing and liquid-heating and dual-temperature piping. Kingflex K1 insulation tube is ideal for applications in:

Ductwork

Large piping and fittings

Tanks

 Vessels

 Cured and irregular surfaces and all types of fitting corers

Kingflex K1 insulation tube is installed using KingGlue 520,520E or 520LV Adhesive.. For application to large,flat or cured metal surfaces full adhesive coverage attachment is applied.

When installed outdoors,KingPaint,a weather-resistant protective finish, is recommended to be applied over the surface to achieve maximum UV protection.

6.Packing and Loading:

Standard kingflex export cartons for tubes, tubes with length 1.83m or 6ft, 300cartons go into 1*40HQ container; tubes with length 2m, 265cartons go into 1*40HQ container.

7.Installation:

NBR/PVC rubber foam heat insulation tube (pipe) for HVAC

Ads by Google


About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9