1)5hours testing before delivery 2)Low noise,low fuel consumption 3)good dynamic performance 4)safe, reliable & economical
Specification of natural gas genset as follows:
1.Main technical performance parameter:
a) No-load voltage setting range:≥ 95-105%
b) Steady state voltage regulation rate : ≤ ±1%
c) Transient state voltage regulation rate: ≤ -15% - +20%
d) Voltage recover time: ≤ 2s
e) Voltage fluctuation rate: ≤ ± 0.5%
f) Steady state frequency regulation rate: ≤ 5%
g) Transient state frequency regulation rate: ≤ ±10%
h) Frequency stabilization time: ≤ 3s
i) Line-voltage waveform sinusoidal distortion rate: ≤ 2.5%
j) Voltage fluctuation rate(between cold state and hot state): ≤ 2%
2.Details
Technical Data |
|
Model of Genset | GF-200-NG |
Model of Engine | 12V138ZQ |
Max. Output of the Engine (KW) | 200KW |
Speed of Engine(RPM) | 1500 |
Number of Cylinder | 4 |
Cylinder Arrangement Type | V |
Strokes of Cylinder | 4 |
Displacement(L) | 26.9 |
Bore/Stroke(mm) | 138/150 |
Air Intake System | Natural Aspiration |
Combustion System | Electronic Ignition |
Compression Ratio | 11.5 |
Cooling System | Water Cooled |
Temperature of Exhaust Smoke (oC) | ≤680 |
Consumption of Nature Gas 100%(G/KW.H) | ≤230 |
Lub. Oil Consumption100% (G/KW.H) | ≤1.5 |
Standard Reference Conditions: | Intake Air Temperature: 25oC; Altitude: 1000m; Ambient Temperature5-40 oC; Air Relative Humidity: No more than 90%. |
Dimension | 2950*1070*1800 |
Weight(kg) | 2200 |
200kw Gas Generator Set