Welcome to ECBAY
CO Detector
CO Detector

Analog and dry contact outputs Electrochemical CO sensor With or without LCD display Wireless of ZigBee or 433M protocal

Sensors

Gas Sensor

Electrochemical carbon monoxide sensor

Sensor lifetime

Up to 5 years, replaceable

Warm up time

1hour (first time)   

Response Time

Within 60 seconds

Signal Update

1s

CO Measuring Range

0~500ppm(default)/0~1000ppm  selectable

Accuracy

<1ppm (at 20±5°C/ 50±20%RH)

Stability

±5% (over 900 days)

Temperature & Humidity Sensor (optional)

Temperature

Relative Humidity

Sensing element:

Band-gap-senor

Capacitive humidity sensor

Measuring range

-20°C~60°C

0 -100%RH

Accuracy

±0.5°C (20~40°C)

±4.5%RH (25°C, 15%-85%RH)

Display resolution

0.1°C

0.1%RH

Stability

±0.1°Cper year

±1%RH per year

Outputs

LCD Display (optional)

Display CO measurement

or CO+ temperature& humidity measurements

Analog Output

1X0~10VDC or 4~20mA linear output

Analog Output Resolution

16Bit

Relay dry contact Output

Up to two dry-contact outputs

Max, switching current 3A (230VAC/30VDC), resistance Load

Modbus Interface

Modbus RS-485 with 19200bps(default), other rates selectable

in the order. 15KV antistatic protection

Electrical and General Items

Power Supply

24VAC/VDC                

Power Consumption

2.8W

Wiring Standard

Wire section area<1.5mm2

Working Condition

-0°C~50°C(32~122°F); 0~99%RH, non condensing

Storage Conditions

10~50°C(-40~158°F)/ 10~70%RH

Net Weight

260g    

Manufacturing Process

ISO 9001 Certified

Housing and IP class

PC/ABS fireproof plastic material, protection class: IP30

Compliance

EMC Directive 89/336/EEC

 

1.Design for real-time detection air carbon monoxide.

2.High accuracy humidity and temperature detection optional

3.With LCD or without LCD selectable

4.Excellent electrochemical CO sensor with up to 5 years lift time

5.Replaceable CO sensor

6.Provide 1X analog linear output (0~10VDC/4~20mA selectable) for the measurement

7.Providing up to two dry contact outputs with presetting the setpoint

8.Modbus RS485 communication interface optional

9.Wireless of ZigBee or 433M protocol optional

10.Provide two easy methods for calibration and setup alarm points by end users: infrared remote controller or a software via RS485

11.24VAC/VDC power supply

CO Detector

Ads by Google


About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.