1, three starting mode: A, voltage ramp departure start to get the maximum output torque, B, constant current limit soft start

External terminals Introductions

ClassfiyTerminal MarkTerminal Namespecification
Main CircuitR.S.TAC main circuit power inputConnect 3 phase AC through breaker
U.V.WSofter output terminalConnect three-phase asynchronous
L21.L22.L23Externalbypass contactor special terminal Connect bypass contactor
Power Control13Power control input terminalConnect AC 220V 50Hz
14
12Earthing terminalEarth Connection
Control CircuitRelay Output1Bypass contactor control terminalsStart after the completion of the closureCapacity:AC 220V 5A
2
3Break contactor output terminalsFailure occurs (Way could set)Capacity:AC 220V 5A
4
5Multifunction output terminalsaction method could programmableCapacity:AC 220V 5A
6
DigitalOutput7External reset terminalsFailure occurs,external terminals reset signal
8Urgency stop control terminalsExternal terminals control emergency stopping signal
9External control stop termialsExternal control,STOP and COM closed,RUN and COM closed means effective,or STOP means effective
10External control run terminals
11External common terminalDigital input common treminals
RS 485ARS485 Positive signalsRS485 terminal
BRS485 Negative signals
Power InterfacePositive 5V Power
GNDGND terminalGND
 GND0-20ma,4-20ma,analog quantity output signal,choose throug program
 FMCurrent signal output terminal

Technical specification

Operationoperational controlkeyboard /external terminals/RS485
start up typecurrent-limiting/voltage/heavy load
start/stop timedigital setting
start delay timedigital setting
emergency stopsuspend the output of soft starter
limiting currentcurrent-limiting and heavy load,starting current operate below this value
starting voltageVoltage,starting voltage could digital setting
underloading controlfind some trouble like belt trips
repeat startingrestart
Bug outputtouch output,AC220V,1A.DC 30V 1A
multifunction relay outputstart delayed ,start,operation,stop,restart
analog output0-20MA,4-20MA for choosing
defencivefunctionsoft starter protectionover current,overload, overheating, unbalanced three-phase,light load, external problem etc
soft starter alarmemergency stopping,light load,restart etc
Displayoperation informatinget ready for state,start delayed,stop etc
parameter protectionprotect the setting parameter isnot change
Service conditionsuse categoryAC-53b
Rated insulation voltage660V
Rated impulse withstand voltage Uimp4KV
operation frequency≤12 times/hour
protection levelCDRA011T4-CDRA055T4:IP20CDRA075T4-CDRA600T4:IP00
Rated limited short-circuit currentCDRA055T4:6KA   CDRA160T4:12KACDRA320T4:20KA CDRA600T4:48KA
Environmentenvironment temperature-0°C to 40°C
store environment-20°C to 65°C
environment humiditymax 90% RH
height/vibratebelow 1000m,5.9m/s2(=0.6g)below
Application sitenon-corrosive gases, flammable gas, oil mist live dust etc
Type of coolingnature wind cooling