Welcome to ECBAY
Photovoltaic System Cable (PV1-F)
Photovoltaic System Cable (PV1-F)

Tinned Flexible Copper No Halogen PO Insulation&Sheath Photovoltaic System Cable. Applied to solar panels,ultraviolet preventio

  1.Executive Standard:

        PV cable(photovoitaic module cable) refers to original draft made out by PV system cable work team of German Standard Committee(Technical Specification 2PFG1169/08.2007 in Rhein TUV company German).

2.No-haogen PV-Cable Type:

         PV1-F: Tinned Flexible Copper Wire No Halogen PO Insulation&Sheath Photovoltaic System Cable.

3. Application

       Applied to  solar panels for power generation and related components of the wiring, connection,particularly suitable for outdoor . Resistance to sunlight, anti-aging , Using the low smoke halogen-free flame retardant materials, higher grade, more safety .

4.Cable Characteristics

MODEL                  PV1-F
ConductorTinned copper wire,class 5 (as per IEC 60228)
InsulationNo Halogen PO insulation
SheathNo Halogen PO sheath
rated voltageAC  0.6/1KV
 DC  1.8KV
Temperature range-40°C~+90°C,dry/ humidity
Max.working temperature of conductor 120°C
During short circuit 200°C
StandardEN 2PFG 1169

5.PV1-F  Structure Parameter 

  type     Cross Sectional Area(mm2)Conductor structure( Strand /mm)diameter(mm)insulation thickness(mm)sheat thickness(mm)cable diameter(mm)DC resistance at 20°C(Ω/km)
 PV1-F      1.5     48/0.2    1.6    1.0    0.8    5.2      12.2
 PV1-F      2.5     77/0.2    2.0     1.0    0.8    5.6     7.56
 PV1-F       4     56/0.3    2.6    1.0    0.9    6.4      4.7
 PV1-F       6     84/0.3    3.2    1.0    0.9    7.0     3.11
 PV1-F      10    77/0.41    4.4    1.0    0.9    8.2     1.84
 PV1-F      16   119/0.41    5.5    1.0    1.1    9.7     1.16
 PV1-F      25   189/0.41    6.5    1.2    1.2   11.3    0.734
 PV1-F      35   244/0.41    7.5    1.2    1.2   12.3    0.529

6.Current Capacity Reference Value

(Ambient Temperture:60°C,Max. Conductor Working Temperature:120°C)

Nom.Area(mm2)Single core in the air(A)Single core on the equipmnt surface(A)Next to equipment(A)
1.5302924
2.5413933
4555244
6706757
10989379
16132125107
25176167142
35218207176

 7.Temperature deviation means conversion factor(as per 60364-5-52)

Ambient Temperature(°C)Conversion FactorAmbient Temperature(°C)  Conversion FactorAmbient Temperature(°C) Conversion Factor
 ≤60 1.00   ≤80 0.82   ≤100 0.58
 ≤70 0.91   ≤90 0.71   ≤110 0.41

     

  

 