Cabinet TEC Air Conditioner/ YX-DC120-W/ DC-48V
Cabinet TEC Air Conditioner/ YX-DC120-W/ DC-48V

1. Cabinet TEC Air conditioner 2. DC48V 3. without compressor 4. door-mounted installation 5. 120W useful cooling output

Cabinet TEC Air Conditioner 

1 Overview

The TEC technology is based on the “Peltier effect ”of the semiconductor. When TEC chip ends connect DC,one End refrigeration, the other end is heating ,the temperature difference between the two ends can be as high as 68°C 

Thermoelectric semiconductor (TEC) refrigeration mesh Former gradually become battery intelligent management technology, especially mobile communication base station outdoor battery cabinet constant temperature control The mainstream choice.

TEC air conditioning have counter-attack joint function, if the dc power supply cord joint reverse, TEC air conditioner doesn't work, back to normal after connection can work normally.

TEC technology has the following characteristics:

1. zero pollution, zero emissions. Safe and reliable;

2. small size, can be door-mounted. Facilitate the realization of the intelligent temperature control and remote monitoring;

3. continuous running, quiet operation. Maintenance-free;

4. can cooling and heating ,easy conversion.

2.Technical Parameters

DC operating voltage

VDC

-60 - 44

Rated Power

W

170

Rated Current

A

3.2

Rated voltage

VDC

-53.5

Cooling capacity

W

125

Heating capacity

W

250

Installation way

Door installed

Operating Temperature Range

°C

-40 - +55

Ambient humidity 

RH

5% -95%

Protection level (between internal recycle and external recycle)

55

Noise level (sound pressure)

Db (A)

<65

Weight

Kg

5.5

3 .product features

1.TEC air conditioning should be able to automatically save the current running state and has the power self-start function.

2.Control functions: air conditioner running automatic control completely based on the internal temperature of the cabinet, Controller through internal cycle Ring temperature sensor Testing machine cabinet return air temperature,And set point comparing judgment ,to control internal and external fan or TEC module work.

3.1 Refrigeration

The cooling open point = cooling stop point + cooling sensitivity , when cabinet internal temperature exceeds cooling open point, start cooling operation.when the inside temperature lower than the cooling stop point, cooling operation stops.

cooling parameters set point

Parameter

The default value

Unit

Description of the set point

The cooling open point (T1)

35

°C

The temperature point when the cooling start

The cooling stop point (T2)

25

°C

The temperature point when the cooling stop

cooling sensitivity 

10

°C

The temperature point when heating start

3.2. Heating

Heating stop point = heating open point + heating sensitivity, when cabinet internal temperature higher than heating open points, begin heating .when cabinet internal temperature higher than heating stop point ,heating operation stop.

Heating parameter set point

Parameter

The default value

Setting range

Unit

Description of the set point

Heating start point (T1)

5

[-10 -15]

°C

The temperature point when the heating start

Heating sensitivity (T2)

5

[5-10]

°C

The sensitivity of the temperature control

3.3 Self-Test

The air conditioner self-test is for field detection use. Self-test procedures are as follows: LED light self-test two seconds, to check whether display normal.Internal and external fan and TEC module get through power to operate 20 second,Inside fan, outside fan and TEC module stop running 8 seconds

Other Air Conditioner: