Welcome to ECBAY
Residential Ground Source Heat Pump
Residential Ground Source Heat Pump

Type:classic serie Modification:Heating in winter, cooling in summer (active and passive),domestic hot water

Specification

NameResidential Ground Source Heat Pump
State of originChina
Typeclassic serie
ModificationHeating in winter, cooling in summer (active and passive),domestic hot water
SourceElectricity, ground water or soil
Cooling Capacity10.4~39.2kW EEP: 5.18 ~6.01
Heating Capacity10~26kW COP: 2.9~4.7
Target GroupVillas
Target AreaAvailable water surrounded or sufficient garden area
Proper working condition

Water temperature in winter is above 12oC, in summer below 35oC; sufficient area for geothermal heat exchangers

Datasheet

classic Series Soil Source Heat Pump PREIUM

ModelHeating Capacity KWCOPCooling Capacity KWEERWater FlowRefrigerant Power V/Ph/HzDimention H×W×D (m)
SourceLoad
m3/h
classic 010 BW-P 11.0 3.0 13.0 5.0 2.6 2.2 R410A380/3/501.15×0.44×0.4
classic 013 BW-P12.8 3.0 14.5 4.6 2.9 2.5 R410A380/3/501.15×0.44×0.4
classic 016 BW-P16.7 3.1 19.6 4.8 4.0 3.4 R410A380/3/501.15×0.44×0.4
classic 020 BW-P21.0 3.1 24.7 4.9 5.1 4.2 R410A380/3/501.0×0.6×0.6
classic 026 BW-P25.5 3.3 29.5 5.1 6.0 5.1 R410A380/3/501.0×0.6×0.6
classic 037 BW-P37.2 3.3 43.7 4.8 9.0 7.5 R410A380/3/501.52×0.8×0.74
classic 049 BW-P47.1 3.2 56.1 4.8 11.6 9.6 R410A380/3/501.52×0.8×0.74

classic Series Soil Source Heat Pump STANDARD

ModelHeating Capacity KWCOPCooling Capacity KWEERWater FlowRefrigerant Power V/Ph/HzDimention H×W×D m
SourceLoad
m3/h
classic 010 BW-S 10.3 3.4 12.0 4.8 2.5 2.0 R22380/3/501.15×0.44×0.4
classic 013 BW-S12.4 3.3 14.1 5.0 2.9 2.4 R22380/3/501.15×0.44×0.4
classic 016 BW-S16.0 3.4 18.2 4.9 3.8 3.1 R22380/3/501.15×0.44×0.4
classic 020 BW-S19.4 3.3 22.0 4.7 4.6 3.8 R22380/3/501.0×0.6×0.6
classic 026 BW-S24.9 3.3 28.0 4.6 5.9 4.8 R22380/3/501.0×0.6×0.6
classic 037 BW-S37.1 3.1 43.3 4.6 9.0 7.4 R22380/3/501.52×0.8×0.74
classic 049 BW-S49.0 3.2 54.2 4.6 11.3 9.3 R22380/3/501.52×0.8×0.74

Remark:

Heating mode operating point : Heat source side water inlet 0°C. Outlet-3°C

                                                  Heat load side water inlet 40°C. Outlet 45°C

Cooling mode operating point : Heat source side water inlet 25°C. Outlet30°C

                                                  Heat load side water inlet 12°C. Outlet 7°C