Feature:
Programmable for various input signals and
measuring ranges.
Configurable without Power Connected.
Din Rail Mo
The Din Rail converter is user configurable using our software on your PC/notebook or our dedicated handheld programmer. The easy to use software is available free from your supplier or can be downloaded from our web site and should be used in conjunction with the URC-1020 USB cable which incorporates an interface converter necessary for communications.The ISC converter can be configured without any loop or power connected making it easy to configure in the workshop before installation. |
|
Specification: |
| |
| Input | Thermocouple (T/C) : industry standard thermocouple types J, K, T, E, B, R, S, N, C (ITS-90). | Pt100: Excitation 180uA. 2 or 3 wire connection (ITS-90 α =0.00385). | Voltage: -60mVdc to 60mVdc or –10Vdc to 10Vdc. | Current : 0-24mAdc | Accuracy | Refer to Table 1 Input Signal | A/D Resolution | 16 bits | Input Sampling Rate | <200ms | Power Supply | DC 24V | Output | Current Output: 4~20mA( Resistive load 600Ω max.) | Continuous Voltage Output: 0~50mV; 0~10V…( Resistive load 600Ω min.) | Output Resolution | 0.6 μ A(15 bits) | Output Response Time | <200ms | Common Mode Rejection Ratio(CMRR) | >80dB | Electromagnetic Compatibility (EMC) | En 50081-2, En 50082-2 | Galvanic isolation | 3.75 KV. between input and output | Operating Temperature | -40 to 85 ° C | Humidity | 0 to 90% RH | Dimension | 75mm(W)x87mm(H)x18.5mm(D) |
Table 1 Input Signal | Input signal | Maximum Range | Accuracy | Thermocouple J | -50 to 1000 ° C (-58 to 1832 ° F ) | 1 ° C | Thermocouple K | -50 to 1370 ° C (-58 to 2498 ° F ) | ± 1 ° C | Thermocouple T | -270 to 400 ° C (-454 to 752 ° F ) | ± 1 ° C | Thermocouple E | -50 to 700°C (-58 to 1292°F) | ± 1 ° C | Thermocouple B | 0 to 1750 ° C (32 to 3182 ° F ) | ± 2 ° C (Note1) | Thermocouple R | -50 to 1750 ° C (-58 to 3182 ° F ) | ± 2 ° C | Thermocouple S | -50 to 1750 ° C (-58 to 3182 ° F ) | ± 2 ° C | Thermocouple N | -50 to 1300 ° C (-58 to 2372 ° F ) | ± 2 ° C | Thermocouple C | -50 to 1800 ° C (-58 to 3272 ° F ) | ± 2 ° C | Pt100 | -200 to 600 ° C (-328 to 1112 ° F ) | ± 0.2 ° C | mV | -60mVto 60mV | ± 0.01m V | Voltage (Note2) | -10 to 10Vdc | ± 1m V | Current (Note2) | 0 to 24mAdc | ± 10μA |
| Note 1 : Accuracy is not guaranteed between 0 and 400°C (0 and 752°F) for type B. Note 2 : The internal DIP switch should be set. | |
|
|
ISC Dual Channel Isolated Signal Conditioner/Converter