Welcome to ECBAY
humidity absorber
humidity absorber

1.Made China's first rotor DH 2.With 30 years professional experience of DH 3.Draw up the national and industry standard of DH

DH-Dehumidifier

Working principle

Character

1)        Combine freeze-drying with further desiccant rotor dehumidify, output constant temperature and humidity dry air, suitable for situations which have requirements on both humidity and temperature.

2)        Inlet air filter, silica gel desiccant wheel, double cold-water heat exchanger;

3)        Chain drive, reliable.

4)        Reactivation by electric heating or steam heating, energy-saving.

5)        Efficient centrifugal fans, stable operation and low noise.

6)        Aluminum alloy frame, high pressure polyurethane foam layer and double colorful steel plate cabinet, anti-cold bridge,;

7)        Electric multi-protection ,safe operation

8)        Reliable PLC control system or pro-cyclical control.

Model Example

ZLB-D-1000

ZLB: low humidity dehumidifier units basic code 

D: Rotary regeneration type. D for Electricity, Z for Steam.

1000: Process airflow m3/h

Main Parameters of ZLB Series Dehumidifier

Main Parameters /  Model 

ZLB-1000

ZLB-5000

ZLB-10000

Process Air

Airflow m³/h

1000

 5000

10000

Fan Power kW

1.1

4.0

7.5

Regeneration Air

Airflow m³/h

340

1650

3450

Fan Power kW

0.25

1.5

3.0

Regeneration Mode

Electrical Heating Power kW

8.4

36

84

Steam Consumption kg/h

14

60

140

Outlet Air

Temperature °C

22±2

Relative Humidity %

≤20

Drive Motor Power kW

0.06

0.12

0.16

Installed Power

Electrical Heating  kW

9.81

41.62

94.68

Steam Heating kW

1.41

5.62

10.68

Overall Dimensions

Length  mm

5000

5700

6000

Width  mm

800

1230

1630

Height  mm

1800

2300

2650

Weight kg

1200

1800

2400

Supporting System Refrigerating Capacity kW

10.0

49.9

99.8

Frozen Water Consumption t/h

1.7

8.6

17.2

Note:

1. Parameter of fresh air: 35°C, 80%

2. The ratio of fresh air is 5% of air output.

3. Output air excess pressure ≥200Pa

4. Supporting system refrigerating capacity and frozen water consumption, you only need to choose one. 

Main components

Desiccant rotor

  

 Cooling Coil

    

Electrical,Text Display

 PLC

humidity absorber

Ads by Google