Magnetic electric contactor Working current: 6A, 9A, 12A Rated frequency: 50/60Hz Standard:IEC60947-4, GB-14048.4
EBS1C-K Magnetic electric contactor
Normal Application and Installation Conditions
(1) Ambient temperature: the upper limit shall not exceed +40C; the lower limit shall be not less than -5C; the average value within 24 hours shall not exceed +35C.
(2) Altitude: installation altitude shall not exceed 2000m.
(3) Atmosphere condition: relative humidity shall not exceed 50% when ambient temperature is +40C. Higher relative humidity is permissible at lower temperature. The average temperature shall not exceed +25Cin the most humid month when the relative humidity shall not exceed 90%. Please consider the dew with the change of temperature.
(4) Anti-pollution degree: III
(5) Installation category: III
(6) Installation conditions: slant of contactor mounting surface shall not exceed ±5.
(7) Shock: contactor can be installed and used in the place where with no notable shock, shake and impact.
Table 1
Model Parameter | EBS1C-06K | EBS1C-09K | EBS1C-12K | ||||
Rated voltage(V) | 660(690) | ||||||
Rated current(A) | 380V | AC-3 | 6 | 9 | 12 | ||
AC-4 | 2.6 | 3.5 | 5 | ||||
Agreed thermal current(A) | 20 | 20 | 20 | ||||
Max. making- current(A) | 380V | 60 | 90 | 120 | |||
660V | 72 | 108 | 144 | ||||
Max. breaking-current(A) | 380V | 48 | 72 | 96 | |||
660V | 60 | 90 | 120 | ||||
Controllable 3-phase squirrel- cage motor power AC3 (KW) | 220V | 1.5 | 2.2 | 3 | |||
380V | 2.2 | 4 | 5.5 | ||||
660V | 3 | 5.5 | 7.5 | ||||
Electrical life | Electrical life | AC-3 | 1200 | ||||
AC-4 | 300 | ||||||
Electrical life (1/h 104 times) | AC-3 | 100 | |||||
AC-4 | 20 | ||||||
Mechanical life(1/h 104 times) | 1000 | ||||||
AC coil consumed power(W) | 2 | ||||||
DC coil consumed power(W) | 4 | ||||||
Wire (mm2) | 1.5 | ||||||
Suitable fuse | NTOO-16 | ||||||
Standard | IEC60947-4, GB-14048.4 |
EBS1C-K Magnetic electric contactor