Detailed Product Description
DXL earth leakage circuit breaker(elcb,circuit breaker)
1.Application
DXL series of leakage circuit breaker is applied for AC 50Hz,rated voltage 230V,which can be used for household and similar estalishments,and also used for human indirect contact protection and the prevention of device leakage current caused by the accident.
It conforms to standard of IEC61001-1 and GB16917.1.
2.Specification
1) Rated voltage(V):AC 230/240 DC230/240
2) number of poles:2P,4P
3) Rated current(A):16,20,25,32,40,50,63,80,100
4) Rated residual operating current(I)(Ma):10,30,100,300,500
5) Rated residual non-operation current(Io)(Ma):≤0.5I
AC 400/415 DC400/415
6) Residual operating current scope:0.5I~I
7) Residual current off-time:≤0.3s
8) Short circuit capacity(Icu):3000A
9) Enduance:4000
10) Protection degree:IP20