Detailed Product Description
Overload protector 3Amp----50Amp
Engineering Information:
Rating:3 Amp-50Amp
Input power:125/250 Vac 50dc 50-60Hz
Interrupting Capacity:1000 Amp × 125Vac 200Amp ×250Vac
Dielectric Strength: 1500Vac 1minute
Resettable Overload Capacity :10 times rated current
Voltage Drop: Less than 0.25V
Insuiation Resistance:>500M ohms
Reset Time: Within 60 seconds
Temperature Rise at Terminal Block: Less than 65oC at 100% of rated curent appiled continuously at 25oC
Contact Endurance: 125Vac×150% of rated current >500 cycles
Calibration(25oC)
100% of rated current:Hold,No-Trip
150% of rated current:Trip in 1 Hour
200% of rated current:Within 40 seconds Trip
300% of rated current:Within 10 seconds Trip
Current Rating in Amp Maximun Resistance in ohms
3-4Amp <0.05
5-6Amp <0.04
7-8Amp <0.025
9-11Amp <0.02
12-13Amp <0.01
14-16Amp <0.008
17-25Amp <0.007
26-35Amp <0.006
40-50Amp <0.005