Welcome to ECBAY
Vacuum interrupter for outdoor circuit breaker 12KV 630A
Vacuum interrupter for outdoor circuit breaker 12KV 630A

1.Once Seal-Exhaust Technique 2.Free painting technology 3.316L Stainless steel, easy-welding and environmental friendly

Main Technical Data 

Rated voltage                                            kv12
Rated current                                            A630
Rated frequency                                         Hz50
Rated short-time power frequency withstand voltage(1min)     kv48
Rated lighting impulse withstand voltage                     kv85
Rated short-circuit breaking current                         kA12.5/16/20
Rated short-circuit making current(peak)                    kA31.5/40/50
Rated operations of short-circuit breaking current interruption   times30
Rated single capacitor bank breaking current                  A400
Rated short-time withstand current                         kA12.5/16/20
Rated peak withstand current                               kA31.5/40/50
Rated duration of short-circuit                              s4
Mechanical life                                           times10000
Contact closing force due to bellows and atmosphere          N70±40
Counterforce at rated contact stroke                          N120±50
Circuit resistance at rated contact force                      μΩ≤20
Shelf life                                                  years20
Contact erosion limit                                       mm3
Weight of moving parts                                                                             kg≤0.7
Mechanical Data Required For Matched Vacuum Switchgear                                             
Rated contact stroke                                      mm9±1
Average opening speed                                   m/s1.0±0.25
Average closing speed                                    m/s0.65±0.15
Added contact force                                       N900/1300/1600±100
Contact bouncing duration at closing operation                ms≤2
Contact bouncing bank amplitude of opening operation         ms≤2
Three-pole simultaneity                                     ms≤1

Note:Rated characteristics can be customised on requirment

Dimension Drawing:

Vacuum interrupter for outdoor circuit breaker 12KV 630A

Ads by Google


About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.