12KV Outdoor Vacuum Circuit breaker (1)Suit for three-phase A.C50Hz (2)Rated voltage:12KV (3)Rated current:630A

General description:

ZW8-32 Outdoor Vacuum circuit breaker is three-phase A.C 50HZ outdoor high voltage distribution equipment with 12kv rated voltage and below, which can be used for opening and closing loading current, overloading current and short-circuit current. If it is connected with computer remote control system and data wireless transmission terminal etc., the remote opeing and closing function can be achieved. This is the optimum unoil equipment for remarking the town and country’s electric net.

 Application and feature:

It is equipped with CT23 type spring energy-stored operating mechanism. Energy-stored, opening and closing can be achieved by motor or by manual.

Applying ambient conditions:

Ambient temperature should be -40~+40.

The height above sea level should be no higher than 1000m.

Wind pressure should be on more than 700Pa.

It is equivalent to wind speed of 34m/s.

The air filthy should be with in III degree.

Frequently violent vibration should be forbidden.

Construction of ZW8 Vacuum circuit breaker

Integral construction with three-phase in one box

Vacuum circuit breaker

Spring operating mechanism

Insulating system

Conduction loop

Box cover/enclosure

Hermetic parts

Technical data

specification

unit

Data

Rated voltage

KV

12

Rated current

A

630

Rated power-frequency withstand voltage(dry test/ wet test)

KA

42/34

Rated short time withstand current

KA

<20

Rated withstand current(peak)

KA

<50

Rated short-circuit breaking current

KA

<20

Rated short-circuit closing current

KA

<50

Rated lighting impulse withstand voltage

KA

75

Rated duration of short circuit

S

4

Rated making operation of short circuit breaker

CYCLES

30

Other technical data

Rated voltage of store energy motor

V

DC220,110 AC220,110

Power of energy-stored motor

W

200

Power of opening and closing coil

V

~200,~100,~220

Current of closing coil

A

Current of opening coil

A

0.5, 0.99,0.51

Current of overloading release

A

5