SERVICE ENVIRONMENTS AND MAIN TECHNICAL DATA 

1.Power supply

Power lines: three-phase 380V+5% -10% 50Hz+5% -5%

Control linessingle-phase 220V+5% -10%  50Hz+5% -5%

Other ratings of voltage and frequency need special order

2.Rating: short time duty, 15 min       Life time: 40 years   Motor insulationH

3. Normal Service Conditions:                            Table 1                                                                   

    service environment

H1

H2

H3

        Temperature      C°

-2070

-2070

-2060

       Pressure         MPa

00.5

00.5

00.5

    Relative Humidity %

≤100

≤100

≤95

Accumulated Radiation DoseGy

1.9×106

1.9×106

0

Seismic acceleration,in three direction of X,Y,Zg

6

6

6

Seismic spectrum Hz

0.235

0.235

0.235

Event Conditions                                      Table 2

Event Conditions

  LOCA

MSLB

Temperature C°

135200

200 for Transient

153200

200 for Transient

Pressure    MPa

0.3

0.22

Relative Humidity%

100

100

For LOCA and MSLB conditions, chemical spray solutions inside containment consist of 2000 ppm boric acid and 0.75% by weight sodium hydroxide to PH ≤1        

                                       

4. Protection: IP68

GENERAL DESCRIPTION

Series HZD electric valve actuators of Class 1E (abbrev. as Class 1E Actuators) are designed to meet the demand of nuclear power stations and are suitable for the two-position operation of globe  valves, gate valves, throttle valves and diaphragm valves etc. These actuators are conformed to the following standards:

1) IEEE382-1996 IEEE Standard for Qualification of Actuators for Power Operated Valve Assemblies with Safety-Related Functions for Nuclear Power Plants. idt EJ/T531-2001 Qualification of Actuators for Power Operated Valve Assemblies with Safety-Related Functions for Nuclear Power Plants.

2)  EJ/T1022.11-1996 Electric Valve Actuators Used in Pressurized-Water Reactors

3)  JB/T8528-1997 Specifications of Normal Type Electric Valve Actuators

These actuators are divided into three types according to plant service environment:

Type H1: used inside containment, subject to event, radiation and seismic environments (satisfied to Catalog K1 environmental conditions in EJ/T1022.11-96)

Type H2: (a) used inside containment, subject to radiation and seismic environments but without event environment; (b) used outside containment, subject to effect of event, radiation and seismic environments (satisfied to Catalog K2 environmental conditions in EJ/T1022.11-96)

Type H3: used outside containment, without effect of event and radiation but subject to seismic environments (satisfied to Catalog K3 environmental conditions in EJ/T1022.11-96)