Welcome to ECBAY
Analog output CO transmitter
Analog output CO transmitter

1.Carbon Monoxide Transmitter with analog output 2. 0~10V/4~20mA optional 3. RS485 communication

CO Measurement

Gas detected

Carbon monoxide

Sensing element

Battery operable electrochemical sensor

Gas sample mode

Diffusion

Warm up time

1hour (first time)   

Response Time

Within 60 seconds

Signal Update

1s

CO Measuring Range

0~100ppm(default)

0~200ppm/0~500ppm   selectable

Accuracy

<±1ppm (at 20±5°C/ 50±20%RH)

Stability

±5% (over 900 days)

Electrical

 

Power Supply

24VAC/VDC

Consumption

1.5 W

Wiring connections

5 terminal blocks (max.)

Outputs

Linear analog output

1x0~10VDC/4~20Ma selectable in order

D/A resolution

16 bit

D/A conversion accuracy

0.1ppm

Modbus RS485 Communication interface

Modbus RS485 interface

9600/14400/19200(default), 28800 bps, 38400 bps (programmable selection), 15KV antistatic protection

General Performance

Operation temperature

0~60°C(32~140°F)

Operation humidity

5~99%RH, non condensing

Storage conditions

0~50°C(32~122°F)

Net Weight

190g

Dimensions

100mm×80mm×28mm

Installation standard

65mm×65mm or 2”×4” junking box

Housing and IP class

PC/ABS fireproof plastic material, protection class: IP30

Compliance

EMC Directive 89/336/EEC

1)  Wall mounting, real time detect CO level with measuring range of 0~100ppm/ 0~200pm/ 0~500ppm.

2)  Electrochemical sensor which offer several advantages over traditional electrochemical sensors.

3)  With a long life, good long term stability, and high accuracy, the CO sensor is environmentally friendly    

      without risk of electrolyte leakage.

4)  With simple calibration

5) The special design of easy sensor’s replacement makes customers replace sensor easily by

     themselves

6) Full time CO level detection, even the slightest leak can be detected

7) One analog output of the measurement of carbon monoxide concentration with 0~10V/4~20mA selectable

8) Special built-in Self-Zero Correction algorithm. 

9) Modbus RS-485 communication with 15KV antistatic protection, also can be calibrated carbon monoxide